In-HouseEngineer

Home › Calculators › AC Size Chart

AC Unit Size Chart & BTU Calculator

What size air conditioner does this house need? Here is the chart you came for — and an honest account of why the same square footage can mean anything from 2 tons to 5 tons. Includes an oversizing check for a system you already have. Jump to the charts ↓

Built and verified by Kyle Lorinos, PE — HVAC design engineer. See the method and limits →

Screening estimate

Living space only — exclude garage and unconditioned areas.
This matters more than square footage. If unsure, "Average" is the safer assumption.
Above 8 ft adds volume the equipment has to condition.
Screening estimate

Detail

AC size charts

The first chart is the one people look for. Read across a row before you read down a column — the spread within a single row is the important part.

Air conditioner size by floor area and construction — hot & humid climate IECC zones 1–2. For other climates, apply the multiplier in the second chart. Screening estimate only — not a substitute for a Manual J load calculation.
Floor area Older / leaky
~400 sq ft/ton
Average
~550 sq ft/ton
Good / newer
~700 sq ft/ton
High performance
~900 sq ft/ton
6001.5 ton18,000 BTU1.5 ton18,000 BTU1.5 ton18,000 BTU1.5 ton18,000 BTU
8002 ton24,000 BTU1.5 ton18,000 BTU1.5 ton18,000 BTU1.5 ton18,000 BTU
1,0002.5 ton30,000 BTU2 ton24,000 BTU1.5 ton18,000 BTU1.5 ton18,000 BTU
1,2003 ton36,000 BTU2 ton24,000 BTU1.5 ton18,000 BTU1.5 ton18,000 BTU
1,5003.5 ton42,000 BTU2.5 ton30,000 BTU2 ton24,000 BTU1.5 ton18,000 BTU
1,8004 ton48,000 BTU3.5 ton42,000 BTU2.5 ton30,000 BTU2 ton24,000 BTU
2,0005 ton60,000 BTU3.5 ton42,000 BTU3 ton36,000 BTU2 ton24,000 BTU
2,4002 systems4 ton48,000 BTU3.5 ton42,000 BTU2.5 ton30,000 BTU
2,8002 systems5 ton60,000 BTU4 ton48,000 BTU3 ton36,000 BTU
3,2002 systems2 systems5 ton60,000 BTU3.5 ton42,000 BTU
3,6002 systems2 systems5 ton60,000 BTU4 ton48,000 BTU
4,0002 systems2 systems2 systems4 ton48,000 BTU

"2 systems" means the load exceeds the largest common residential unit (5 tons). Above that you are into multiple systems or zoning, which is a design decision, not a chart lookup.

Climate adjustment Multiply the hot-humid square-feet-per-ton figure by this. A cooler climate means fewer tons for the same house.
ClimateIECC zoneMultiplierAverage construction
Hot & humid — S. Florida, Gulf Coast1–2×1.00550 sq ft/ton
Warm — N. Florida, Texas, Georgia3×1.15632 sq ft/ton
Mixed — Mid-Atlantic, Tennessee4×1.30715 sq ft/ton
Cool — Chicago, New England5×1.45798 sq ft/ton
Cold — Minnesota, Maine6–7×1.60880 sq ft/ton
Standard residential equipment sizes One ton = 12,000 BTU/hr. Airflow at 400 CFM/ton is the general default; 350 CFM/ton is common in humid climates because slower air across the coil removes more moisture.
Nominal sizeBTU/hrCFM @ 350/tonCFM @ 400/ton
1.5 ton18,000525600
2 ton24,000700800
2.5 ton30,0008751000
3 ton36,00010501200
3.5 ton42,00012251400
4 ton48,00014001600
5 ton60,00017502000

Note there is no 4.5 ton unit. Equipment comes in half-ton steps to 4 tons, then jumps to 5 — which is exactly where a lot of oversizing happens.

Read across the row, not down the column

Look at the 2,000 square foot line in the first chart. The same house, in the same climate, ranges from 2 tons to 5 tons depending only on how it was built.

That is a two-and-a-half times spread from a single variable that no square-footage chart can see. Insulation levels, air tightness, window area and orientation, duct location, and whether the ductwork leaks into an attic — those determine the load. Floor area only scales it.

This is why every rule of thumb you find online disagrees with every other one. They are all averaging across that spread. The disagreement between sources isn't sloppiness — it's the honest signal that the method can't resolve what you're asking it to.

So use the chart the way it's actually useful: as a sanity check, not a specification. If your house is 1,800 square feet and someone quoted you a 5-ton system, the chart tells you to ask why. If they quoted 3 tons, the chart says that's plausible and the conversation moves on to the real calculation.

Why oversizing is the more common failure — and the worse one

Contractors oversize far more often than they undersize, and the incentives explain it. An undersized system generates a callback in the first heat wave. An oversized one generates a comfort complaint that most people never connect to equipment capacity. One of those failure modes is visible and the other isn't.

But in a humid climate, oversizing is the one that actually hurts.

An air conditioner does two jobs, and only gets credit for one

Cooling equipment removes sensible heat (temperature) and latent heat (moisture). The thermostat only measures the first one. Moisture removal happens because air spends time on a cold coil — water condenses out and drains away — and that requires runtime.

An oversized unit satisfies the thermostat on temperature fast, then shuts off. The coil never gets properly cold and wet, the run cycle is too short, and moisture stays in the house.

The result is the complaint nobody diagnoses correctly: the house hits 74 °F and still feels clammy. So the thermostat goes down to 70, then 68, and it feels worse — because lowering the setpoint doesn't remove moisture, it just makes every surface colder and closer to the dew point. That's when supply registers start sweating and mold appears at ceiling diffusers.

If that describes a house you're looking at, the relative humidity calculator shows why turning the thermostat down makes it feel worse, and the dew point calculator will tell you whether the registers are actually below the dew point.

The other costs

Manual S: the rule that stops this

ACCA Manual S governs equipment selection once Manual J has given you a load. Its central constraint:

Cooling equipment should be selected between 90% and 115% of the calculated cooling load. Not "at least" the load — a bounded window, with a ceiling.

That ceiling is the part routinely ignored. Here's what it means in practice, given that equipment only comes in half-ton steps:

Calculated loadAllowable range (90–115%)Standard sizes that comply
2.4 tons2.16 – 2.762.5 ton only
3.1 tons2.79 – 3.563 or 3.5 ton
3.6 tons3.24 – 4.143.5 or 4 ton

When two sizes both comply, take the smaller one in a humid climate. The smaller unit runs longer, and longer runtime is what removes moisture. In a dry climate the argument is weaker and either is defensible.

Note also the gap between 4 and 5 tons. A house with a 4.4 ton load has no compliant option — 4 tons is 91% (fine) but 5 tons is 114%, technically inside the window and in practice a meaningfully oversized machine. This is where a second system, zoning, or variable-capacity equipment earns its cost.

Variable-capacity equipment changes this calculus

Inverter-driven and two-stage systems can modulate down, so a nominal 4-ton unit might run at 1.5 tons on a mild day. That largely solves the short-cycling problem and is genuinely more forgiving of imperfect sizing. It does not make sizing irrelevant — a badly oversized variable system still has a minimum capacity it can't go below — but it widens the acceptable window considerably.

What a real load calculation accounts for that a chart cannot

ACCA Manual J is the standard, and it's referenced by the IRC. It looks at:

That last point is the real gap. This page can estimate capacity. It cannot tell you the sensible heat ratio, and in a humid climate the sensible heat ratio is the number that decides whether the house is comfortable.

Checking a system you already have

Switch the tool above to "Check if my current system is oversized" and it will report your square feet per ton against the typical band. Treat that as a screening result — but it pairs well with two things you can observe directly:

  1. Time a run cycle on a hot afternoon. Fifteen to twenty minutes is healthy. Consistent five to eight minute cycles when it's 90 °F outside strongly suggests oversizing.
  2. Put a hygrometer in the main living space. If the system is holding temperature but indoor RH sits above 55–60%, the equipment is not getting enough runtime to dehumidify. A cheap digital hygrometer costs about fifteen dollars and settles the argument.

Those two observations together are worth more than any chart on this page.

The honest bottom line

If you're replacing a system, the right sequence is: Manual J for the load, Manual S for the equipment, Manual D for the ducts. Skipping to equipment selection is how houses end up cold and clammy with a brand-new system in them.

A contractor who runs a real load calculation and shows you the output is telling you something meaningful about how they work. One who sizes from square footage, or simply matches whatever was there before, is repeating whatever mistake was made last time.

If the stakes justify an independent calculation — a new system, a major renovation, or a comfort problem nobody has been able to solve — that's what my practice does.

Method and limits

What this tool actually computes

A square-feet-per-ton screening estimate, adjusted for climate, construction quality, glazing exposure and ceiling height:

tons = (floor area × height factor × glazing factor) / (base sq ft per ton × climate multiplier)

Base figures are 400 / 550 / 700 / 900 sq ft per ton for older-leaky / average / good / high-performance construction in IECC zones 1–2. Climate multipliers run 1.00 to 1.60 from hot-humid to cold. Height factor is the ratio of actual ceiling height to 8 ft, applied at 60% weight, because volume affects load less than proportionally.

Results are rounded to the nearest standard nominal size, and both the next size up and down are shown, because the rounding decision is often more consequential than the estimate itself.

Where the base figures come from

These are representative of commonly published rules of thumb and of loads seen in practice in South Florida. They are not a standard. No authority publishes an official square-feet-per-ton value, because the profession's position — correctly — is that the method is inadequate for equipment selection. Published rules of thumb vary by roughly a factor of two, which is stated plainly above rather than hidden behind a single confident number.

ACCA Manual S selection window

Cooling equipment total capacity between 90% and 115% of the calculated sensible-plus-latent cooling load. Heat pumps in heating mode allow more latitude. The tool applies the 90–115% window to its own estimate to show which standard sizes would comply, which is illustrative — the window is meant to be applied to a Manual J result, not to a screening estimate.

Limitations — read these